CCT-8920 Conductivity Transmitter instruction
The pipeline installation: conductivity data collection valve for water treatment process all the installation.
Category:
Keywords:
Product details
Applications
• The pipeline installation: conductivity data collection valve for water treatment process all the installation.
• The open installation: all open channel, hydrology, water, ocean conductivity (salinity) monitoring open installation;
• The wall installation : the conductivity cell using soft connection as a form of industrial field acquisition, the transmitter is installed on the wall.
• The anchor drift installation: applied in hydrology, marine remote solar powered wireless data transmission;
Over View
CCT-8920 Conductivity/Resistivity Transmitter adopts 128x64 resolution dot-matrix liquid crystal display screen, white background backlight, conductivity/resistivity/temperature/transmission parameter can be displayed in the same screen. It has a simple structure, cost-effective features.
Technical Parameters
|
Transmitter name
|
CCT-8920 Series Two-wire conductivity/Resistivity transmitter
|
|||
|
Measurement range
|
(0.05~18.25 )MΩ.cm
|
(0.5~100)μs/cm
|
(1.0~1000) μs/cm
|
(0.05~10)ms/cm |
|
Constant
|
0.01 cm-1
|
0.1 cm-1
|
1.0 cm-1
|
10.0 cm-1
|
|
Material
|
316L Stainless steel
|
Stainless steel
|
Graphite
|
Graphite
|
|
Accuracy
|
2.0 level
|
1.5 level
|
1.5 level
|
1.5 level
|
|
Stability
|
±0.5% (FS)/24h
|
|||
|
Temperature
|
(0 ~50)℃
|
|||
|
Temperature compensation
|
Conductivity : (0 ~100)℃ linear ; 90℃as standard ,automatic temperature compensation Resistivity : (0 ~50)℃non linear ; 25℃as standard ,automatic temperature compensation |
|||
|
Thermistor
|
pt1000
|
|||
|
Transmitting
|
Isolation
|
measurement is totally isolated from power
|
||
|
output
|
(4~20)mA
|
|||
|
Loop resistivity
|
300Ω(Max),24VDC ;100Ω(Max),20VDC
|
|||
|
Transmitting accuracy
|
±0.1mA
|
|||
|
Power supply
|
DC 24V±4V
|
|||
|
Working conditions
|
Temperature:(0~50)℃ , relative humidity : ≤95%RH ( non-condensing)
|
|||
|
Storage
|
Temperature:(-20~60)℃ , relative humidity : ≤85%RH ( non-condensing)
|
|||
|
Protection level
|
IP65
|
|||
|
Installation
|
Pipe installation /flow cell / immersion type
|
|||
Workshop
Online inquiry