ROC-7000 Reverse Osmosis Control Integrated System
Category:
Keywords:
Product details
Application Fields
Applicable to all kinds of small and medium-sized single-stage, double-stage reverse osmosis control system. With simple operation, complete measurement and configuration, highly integrated system .
Performance Characteristics
• Human-Computer Interface, 7 inch colour touch screen, dynamic process display;
• Conductivity test,raw water, primary and secondary conductivity detection, with ultra-limit alarm and discharge drive;
• Human-computer interaction, pop-up soft keyboard, can set or modify the operating parameters, feature-rich, easy to operate;
• Automatic control, with built-in measurement analysis and DI/DO in control system, embedding the process running software, to achieve highly integration;
• Consumables management, consumables pre-processing capacity, the remaining processing capacity forecast makes the user know the operation of the consumables in time;
• Flush mode, the system flush for boot and shutdown, wash time can be free set;
• pH adjustment,Real-time detection of pH,drive ph adjustment pump to balance pH (two-stage) at any time;
• Set the antiscale metering pump control, and chain with the original pump control.
• Leakage detection, real-time detect the system leakage signal, immediately stop if leakage alarm, to prevent the expansion of the situation;
• Flow detection, record the instantaneous flow of raw water, producing water and concentrated water, to save the cumulative flow;
• Restricted function of concentrated water flow, to avoid illegal operation of membrane components premature fouling caused by the pursuit of high recovery rate;
• Data storage, operating data recalls in the form of historical curves and data queue, make the user easier to compare and record, and has a U disk export function, and for data backup;
• Remote communication, RS485 communication port can achieve remote transmission through GPRS/WIFI or Zigebee and other wireless modules, but also access to the Internet to achieve remote real-time monitoring and fault diagnosis and other functions.
• Extended redundancy, the manufacturer can extend on basis of this series for user needs.
• Panel installation, detection modules are all built-in, so that the external distribution lines are rare, with simple and beautiful installation;
• Good electromagnetic compatibility (EMC) design, calmly deal with complex industrial field electromagnetic environment.
The main measurement technical data
|
Controller type |
Single-stage/Double-stage Reverse osmosis control integrated system |
|||||
|
Conductivity measurement parameters |
Cell constant |
0.1cm-1 |
1.0 cm-1 |
10.0cm-1 |
||
|
Raw water conductivity |
|
(0~2000) μS/cm |
(0~20000) μS/cm |
|||
|
Primary conductivity |
(0~200) μS/cm |
(0~2000) μS/cm |
|
|||
|
Secondary conductivity |
(0~200) μS/cm |
(0~2000) μS/cm |
|
|||
|
Temperature compensation |
Automatic compensation on the basis of 25 ℃ ,compensation range(0~50)℃ |
|||||
|
Accuracy |
Matched precision:1.5 level |
|||||
|
Flow measurement range |
Instantaneous flow |
(0~999)m3/h |
||||
|
Accumulative flow |
(0~9999999)m3 |
|||||
|
pH measurement parameters |
Measurement range |
2-12 |
||||
|
Accuracy |
±0.1pH |
|||||
|
Temperature compensation |
Automatic compensation on the basis of 25 ℃ ,compensation range(0~50)℃ |
|||||
|
DI acquisition |
Input signal |
Low pressure switch of Tap water,high level of pure water tank, low level of pure water tank, low pressure switch before the pump, high pressure switch after the primary booster pump,high level of secondary pure water tank, low level of secondary pure water tank,high pressure switch after the secondary booster pump |
||||
|
Signal Type |
Passive switch contact |
|||||
|
DO Control |
Control output |
Inlet valve, primary flush valve, primary drain valve, antiscalant pump, raw water pump, primary booster pump, secondary booster pump, secondary flush valve, secondary drain valve, pH adjustment metering pump. |
||||
|
Electrical contact |
Relay(ON/OFF) |
|||||
|
Load capacity |
3A(AC 250V)~ 3A(DC 30V) |
|||||
|
Display screen |
Screen color:TFT;resolution:800×480 |
|||||
|
Working power |
Working power |
DC 24V±4V |
||||
|
Power consumption |
≤6.0W |
|||||
|
Working environment |
Temperature:(0~50)℃;Relative humidity:≤85%RH(non condensation) |
|||||
|
Storage environment |
Temperature:(-20~60)℃;Relative humidity:≤85%RH(non condensation) |
|||||
|
Installation |
Panel mounted |
Hole(Length×Width,192mm×137mm) |
||||
Order direction :
ROC-7100 Singe Stage Reverse Osmosis Control Integrated System
ROC-7200 Double Stage Reverse Osmosis Control Integrated System
|
Conductivity probe |
pH probe |
Flow probe |
Water leakage sensor |
|
3pieces (max) |
1piece (max) |
3pieces (max) |
1piece (max) |